Biomass generator (350GFM)
350kW Biomass Generator
This 350kW Biomass Generator is equipped with 8300D/M Gas engine as original power, and possesses the following outstanding characteristics and functions:
A) The output voltage can be 400V, 6300V, 10500V, reducing the initial investment and running cost.
B) Big bore of 300mm ensures its continuous constant power output.
C) Low speed of 500rpm ensures the service life.
D) Natural aspiration ensures the safety of coal bed methane delivery.
E) Easy maintenance and low noise.
MAIN SPECIFICATIONS OF GAS GENERATOR SET
Model |
350GFM |
|
Gas Engine Model |
6300D/M-2 |
Rated power |
350kw |
|
Alternator |
synchronous brushless generator |
Rated voltage |
400 V |
|
Insulation class |
F |
Rated speed |
500rpm |
|
Voltage regulation |
Automatic |
Rated frequency |
50Hz |
|
Class of protection |
IP22 |
Rated current |
631A |
|
Cooling method |
Water cooling with radiator and fan |
Power factor |
0.8 Lagging |
|
Dimension (mm) |
5750×2650×2500mm |
Control mode |
Electric control |
|
Net Weight (kg) |
11800 Kg |
MAIN ELECTRICAL PERFORMANCE OF THE GAS GENERATOR
Voltage |
Stabilized regulation |
Instantaneous regulation |
Recovery time |
Fluctuation |
±2.5% |
+20% |
2 S |
1% |
Frequency |
Stabilized regulation |
Instantaneous regulation |
Recovery time |
Fluctuation |
0-5% adjustable |
≤±10% |
< 7 S |
1% |
MAIN SPECIFICATIONS OF GAS ENGINE
Model |
6300D/M-2 |
Rated power |
438 kW |
Rated speed |
1000 r/min |
Arrange of cylinder/bore of stroke |
300mm |
Stroke of piston |
210mm |
Intake gas pressure required |
7-9kPa |
Heat consumption |
≤11500 KJ/kW·h |
Speed Governor |
Electric governor |
Oil consumption |
£ 0.6g/kWh |
Ignition model |
Spark plug ignition |
Exhaust temperature (before turbine) |
≤ 600℃ |
Start method |
24V DC |
SAFETY AND PROTECTION DEVICE OF THE GENSETS
Output voltage too low/too high alarm and stop |
Single phase connection trouble alarm and stop |
Frequency too high/too low alarm and stop |
Cooling water temp high alarm |
Reverse power alarm and break brake |
Lubrication oil temp too high alarm |
Overload alarm and break brake |
Lubrication oil pressure too low alarm and stop |
Over speed alarm and stop |
Battery voltage too low alarm |
Blast prevention of air inlet and crankcase |
Gas leaking protection |
OPTIONAL DEVICE
♦ Steel Soundproof Container (sound attenuated canopy)
♦ CHP/ Cogeneration/CCHP Trigeneration
♦ ATS and Synchronization Parallelling Panel
♦ Oil and Water Heater